First of all: The issue communication with RA team and discussion... : RA ENIP EDS file issues.pdf
Panel | ||||
---|---|---|---|---|
| ||||
Why does my modular EDS file not work? |
Panel | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||
To support modular functionality it is necessary that the “ProxyConnectN (N = 1, 2,…)” entries are defined in EDS section [Connection Manager] of communication Adapter and the corresponding “ProxiedConnectN” entries are defined in the same section of IO Module. Examples:
Reference:P1219, 7-3.7.2 Modular Additions to Basic EDS Sections, The CIP Networks Library Volume 1, Edit 3.8. April 2010.
|
Panel | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||
|